8.3 Malfunction/maintenance
alarm
All status and fault alarms are assigned to a
classified status in the positioner. The default
settings of the status classification are listed
in the code list.
Note: The status classification can be
changed in TROVIS-VIEW and over the
PROFIBUS-PA parameters.
Refer to the Configuration Manual
KH 8384-4 EN on the supplied CD-ROM
(CD 8384-4) for more details.
To provide a better overview, the classified
alarms are summarized in a condensed
state according to the NAMUR Recommen-
dation NE 107. The following status alarms
are available:
4
Maintenance alarm
The positioner cannot perform its control
task due to a functional fault in the de
-
vice or in one of its peripherals or an ini
-
tialization has not yet been successfully
completed.
4
Maintenance required
The positioner still performs its control
task (with restrictions). A maintenance
requirement or above average wear has
been determined. The wear tolerance will
soon be exhausted or is reducing at a
faster rate than expected. Maintenance
is necessary in the medium term.
4
Maintenance demanded
The positioner still performs its control
task (with restrictions). A maintenance
demand or above average wear has
been determined. The wear tolerance will
soon be exhausted or is reducing at a
faster rate than expected. Maintenance
is necessary in the short term.
4
Process-related faults/outside of specifi
-
cations
The positioner is being operated outside
the specified conditions of use.
4
Function check
Test or calibration procedures are being
performed. The positioner is temporarily
unable to perform its control task until
this procedure is completed.
Note: If an event is assigned to the “No
message” status, this event does not have
any effect on the condensed state.
The condensed state appears on the display
with the following icons:
Condensed state
Positioner
display
Maintenance alarm
Function check Text
Maintenance required/
Maintenance demanded
Process-related faults/
outside of specifications
No message
If the positioner has not been initialized, the
maintenance alarm icon ( ) appears on
the display as the positioner cannot follow
its set point.
If fault alarms exist, the possible source of
error is displayed in Code 49 onwards. In
this case,
Err appears on the display.
EB 8384-4 EN 73
Operation