3.2 Communication
The positioner is completely controlled over
the digital signal transmission implemented
complying with PROFIBUS-PA Profile B as
per DIN EN 50170 and DIN 19245 Part 4.
Data are transmitted as bit-synchronous cur
-
rent modulation at a rate of 31.25 kbit/s
over twisted-pair cables conforming to
IEC 61158-2.
Usually, the positioner settings are made on
a computer which is connected to one or
more positioners linked over a segment cou
-
pler to the PROFIBUS segment of the com
-
puter..
The Configuration Manual KH 8384-4 EN
contains a description on how to configure
and operate the positioner over
PROFIBUS-PA.
3.2.1 Configuration using
TROVIS-VIEW software
The positioner can be configured using
TROVIS-VIEW Configuration and Operator
Interface software.
The positioner is equipped with an addi
-
tional digital SERIAL INTERFACE to connect
the RS-232 or USB port of the computer to
the positioner over an adapter cable.
The TROVIS-VIEW software enables the user
to easily set parameters in the positioner
and view process parameters online.
Note: The TROVIS-VIEW software is a com
-
mon operator interface for various smart
SAMSON devices. The software together
with a device-specific module allow the con-
figuration and parameterization of the de-
vice.
The device-specific module for Type 3730-4
can be downloaded free of charge from the
SAMSON website (Services > Software >
TROVIS-VIEW).
Additional information on TROVIS-VIEW
(e.g. system requirements) can found on the
SAMSON website and in the Data Sheet
T 6661 EN.