4
Out of specification
The positioner is operated outside the
specified operating conditions.
Note: If an event is assigned to the 'No mes
-
sage' status, this event does not have any ef
-
fect on the condensed state.
Condensed state
The condensed state appears on the display
with the following icons:
Condensed state
Positioner
display
Priority
Function check
Text, e.g.
TUNE
or
TEST
Failure
Out of specifica-
tion
blinking
Maintenance re-
quired/ Mainte-
nance demanded
The message with the highest priority deter
-
mines the condensed state in the positioner.
If error messages exist, the possible source
of error is displayed in Code 49 onwards. In
this case,
ERR
appears on the display.
Example:
Error caused by pin
position
The cause and recommended action are
listed in the code list (section 14).
Fault alarm output
The 'Failure' as the condensed state causes
the optional fault alarm output to be
switched.
4
The 'Function check' condensed state can
also activate the fault alarm contact in
Code 32.
4
The 'Maintenance required/ Mainte
-
nance demanded' condensed state and
'Out of specification' can also activate
the fault alarm contact in Code 33.
8.3.1 Confirming error messages
Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Turn
®
Code 3, display:
No
Press , Code 3 blinks
Turn
®
YES
Press , display:
Confirm error messages:
Turn
®
Error code which you want to
confirm.
Press to confirm the error message.
EB 8384-6 EN 77
Operation
S